Quality Marine Products Distributor

Presents

bst Brandschutztechnik


Contact Jastram    Line Card   Product Index   External Links

  

Design

For bst-frame types SB, SS, LB. TCM modules are made from halogen-free and highly fire-resistant elastomeric rubber (HFE).
Module length 60mm.
The revolution in multi cable transits!
The system parts are the "Quick-Basic", "Quick-Adapter" and "Quick-Core". With this system cable diameters in a range of 12mm and higher can be sealed easily and quickly. Available for frames in Register 1 (depth of 60mm) and in Register 2 (depth of 90mm).

 

Quick-Fix 
The new modular sealing system from bst, fire-resistant, gas- and watertight, represents the revolutionary idea of the TCM technology (Tolerance Cable Module). Re-usable sets consisting of Quick-Basic, Quick-Adapter and Quick-Core will seal cables and pipes within a tolerance range of 12mm or more! This saves you money with reduced installation time, pre-planning or layout time, storage space in your stockroom, and it protects the environment. Available in 4 different module sizes (20, 30, 40 and 60mm), insert modules as well as multi insert modules, suitable for all frames found in our technical bulletin "Register 1" (60mm deep frames) and "Register 2" (90mm deep frames).

Quick-Basic
The basic module will seal cables within a tolerance range of 2-3mm! (without a Quick-Adapter)

Quick-Adapter
Two or three adapter modules are supplied with each module to seal cables with diameters in a tolerance range of 3-5mm each!

Quick-Core
Used together with the Quick Adapter "Small" it forms a filler module which will reserve space for future additions or just complete the filling open space in the frame.

TCM-Ruler
In order to facilitate the selection of the correct TCM modules, bst created the TCM-Ruler. With this "measuring tape" you can easily determine the suitable Quick-Fix combination for your cable!

Quick Fix TCM's are supplied in various packing units consisting of several sets or kits.

TCM modules (Quick Fix modules)


Quick Fix insert module p/n CO-TCM-2x15/0+3-5 with core
accepts cables 3 to 5 mm O.D.     length 60mm

Quick Fix insert module p/n CO-TCM-2x15/0+6-7 with core
accepts cables 6 to 7 mm O.D.    length 60mm

Quick Fix insert module p/n CO-TCM-2x15/0+3-5/30 with core
accepts cables 3 to 5 mm O.D.     length 30mm

Quick Fix insert module p/n CO-TCM-2x15/0+6-7/30 with core
accepts cables 6 to 7 mm O.D.    length 30mm

 


Quick Fix insert module p/n CO-TCM-20/0+5-12 with core
accepts cables 5 to 12 mm O.D.



Quick Fix insert module p/n CO-TCM-30/0+13-23 with core
accepts cables 13 to 23 mm O.D.


Quick Fix insert module p/n CO-TCM-40/0+23-33 with core
accepts cables 23 to 33 mm O.D.



TCM modules (Quick Fix modules)


Quick Fix insert module p/n CO-TCM-60/0+33-51 with core
Quick Fix insert module p/n CO-TCM-60/33-51 without core
accepts cables 33 to 51 mm O.D.

Quick Fix insert module p/n CO-TCM-90/0+52-78 with core
Quick Fix insert module p/n CO-TCM-90/52-78 without core
accepts cables 52 to 78 mm O.D.
Quick Fix insert module p/n CO-TCM-120/0+79-99 with core
Quick Fix insert module p/n CO-TCM-120/79-99 without core
accepts cables 79 to 99 mm O.D.

These Quick Fix (TCM) module are available in the following packages


 Set

 Each set consisting of

Packing unit:
box 12x18x6cm
Packing unit:
cart. 39x26x15cm

CO-TCM-2X15/0+3-5
CO-TCM-2X15/0+6-7

 2  Quick-basic  8x15    03-05mm
 8  Quick-cores  o.d.  03, 04 & 05mm
 2  Quick-basic  8x15    06-07mm
 8  Quick-cores  o.d.  06 & 07 mm

Box qty 6 sets each for
88 cables

Carton   8 boxes ea.
for 528 cables

CO-TCM-20/0+5-12

12 Quick-adapter  20/S     05-07mm
12  Quick-adapter 20/L     08-10mm
12  Quick-basic      20          11-12mm
  6  Quick-core        o.d.         5 mm


box qty  6 sets each for
36 cables


Carton   8 boxes ea.
for 288 cables

CO-TCM-30/0+13-23

  8  Quick-adapter 30/S    13-16mm
  8  Quick-adapter 30/L    17-21mm
  8  Quick-basic       30        22-23mm
  4  Quick-core        o.d.       13 mm


box qty  4 sets each for
16 cables


Carton   8 boxes ea.
for 128 cables

CO-TCM-40/0+23-33

  8  Quick-adapter 40/S     23 - 26mm
  8  Quick-adapter 40/L     27 - 30mm
  8  Quick-basic       40         31 - 33mm
  4  Quick-core        o.d.        23 mm


box qty  2 sets each for 
8 cables

Carton   8 boxes ea.
for  64 cables

CO-TCM-60/0+33-51

  2  Quick-adapter  60/S    34 - 38mm
  2  Quick-adapter  60/L    39 - 43mm
  2  Quick-adapter  60/XL  44 - 48mm
  2  Quick-basic       60         49 - 51mm
  1  Quick-core         o.d.          34 mm


box qty  4 sets each for 
4 cables

Carton   8 boxes ea.
for  32 cables
CO-TCM-90/0+52-78

  2  Quick-adapter 90/S     52 - 57mm
  2  Quick-adapter 90/L     58 - 63mm
  2  Quick-adapter 90/XL   64 - 69mm
  2  Quick-adapter 90/XXL 70 - 75mm
  2  Quick-basic      90           76 - 78mm
  1  Quick-core        o.d.          52 mm


Individual

Carton   8 Individuals. for  8 cables
CO-TCM-120/0+79-99

  2  Quick-adapter 120/S   79 - 84mm
  2  Quick-adapter 120/L   85 - 90mm
  2  Quick-adapter 120/XL 91 - 96mm
  2  Quick-basic       120       97 - 99mm
  1  Quick-core         o.d.          79 mm


Individual

Carton   6 Individuals. for  6 cables

Installation


cover inner sides of frame and all rubber parts liberally with bst-lubricant

measure the cable with the TCM Ruler to determine module required

remove core ....

...and insert correct quick adaptor

Install insert- or multi insert modules according to filling plan.

Anchor plates put between the module rows facilitate the assembly and increase sealing effect.

bst multi insert modules reduce assembly time, single half-modules are simply torn-off.

Remaining space to be filled with filler bocks or multi filler blocks. Insert last anchor plate in due time!

Most important : lubricate all inner surfaces of wedge K-120 sufficiently! Put the side wedges around the central wedge...

...and press the K-120 above the last anchor plate into the frame, but apply pressure only to the head of the bolt!

Tighten the bolt with socket I.D. 17 mm and ratchet or electric drill.

finished frame


If at a later date more cables need to be added to the frame, the frame can be opened, the new cable added, and then closed again at any time.

Unscrew central bolt and remove it!

Insert puller screw (attached to puller with a chain) into the tapped hole of central wedge.

Hook puller to the screw and pull out the wedge by wrench I.D. 22mm.



 
Contact Jastram    Line Card   Product Index   External Links

Jastram Logo and page style © Jastram Technologies Ltd.
bst Logo, graphics and text © bst Brandschutztechnik
last updated 31st Oct 2005